What does SFA mean on motor?

Service Factor Amps, or S.F.A., represents the amount of current the motor will draw when running at the full Service Factor. In the example nameplate, the S.F.A. is eight amps at 230 volts. Continually exceeding the S.F.A. shown on the nameplate can shorten motor life.

How do you calculate amp service factor on a motor?

For example, the FLA or full load amps of the motor above is 10.8 amps at 115 volts. The service factor or S.F. is 1.5, making the service factor amps 16.2 (rounded down to 16 on the motor tag) at 115v because 10.8 x 1.5 = 16.2.

What is motor FLA rating?

Full-Load-Amperage (FLA) refers to the motor’s rated-current at rated-load and rated-voltage. This is the amount of current (amps) the motor will draw from the electrical system when producing its rated output horsepower. This value can also sometimes be referred to as: Running Amps, Rated Amps, or just AMPS.

What does SLA mean on a motor?

Full meaning of SLA is “Source Level Adjustment“.

What is SF max amps?

The SFA stands for Service Factor Amps. This is the absolute maximum current that the motor can handle continuously without damage. Most motors have a service factor rating.

IT IS INTERESTING:  Frequent question: How do you find the maximum efficiency of a heat engine?

How do you determine the service factor of a motor?

Multiply your motor horsepower by the service factor. For example, if you have a 1HP motor and your service factor is 1.25, then you can operate safely at an HP = 1.25HP without overheating or damaging the motor.

Should a motor run at FLA?

RE: Running at FLA

If it is a continuous duty rated motor, it should be able to be run at its rated FLA without any problem. However, I would be concerned that if its running at FLA, it may dip into overload under some conditions during the 3 day run. You could check the running temperature at the end of its cycle.

How is motor Fla calculated?

The motor FLA calculator uses the following formulas:

  1. Single Phase AC Motor FLA (Amperes) = (P [kW] × 1000) / (V × cos ϕ)
  2. Single Phase AC Motor FLA (Amperes) = (P [HP] × 746) / (V × cos ϕ × η)
  3. Three Phase AC Motor FLA (Amperes) = (P [kW] × 1000) / (V × 1.732 × cos ϕ)

Is SFA the same as FLA?

Full Load Amps, or F.L.A., represents the amount of current the motor is designed to draw at the rated horsepower. … Service Factor Amps, or S.F.A., represents the amount of current the motor will draw when running at the full Service Factor.

What is SF in gearbox?

What is a service factor exactly? It’s the ratio of horsepower your gear reducer can mechanically handle compared to the horsepower required for your application. Put simply, it is how overdesigned the gearbox is when it comes to handling the application load.